美国人韩国日本A级强奸视频电影|韩国三级a∨在线观看|2020精品国产自在现线官网|国产网友愉拍精品视频手机,|

EDPC-410C2(C3) type microprocessor based capacitor protection and monitoring device


  • Overview
  • Characteristic
  • Selection Guide

EDPC ¨C 410C2(C3) type microcomputer capacitor protection device applies to protection and monitoring for parallel capacitor banks in single Y, double Y, ¦¤ wiring in systems not directly grounded or grounding via resistor with voltage ratings of 380~10kV.

protection function

Index

Protection Function

1

Instantaneous protection

2

Time limit instantaneous protection

3

Definite-time over-current protection, inverse time over-current protection

4

Zero sequence over-current protection

5

Over-voltage protection

6

Low voltage protection ( under-voltage protection)

7

Unbalanced current protection (Unbalanced C)

8

Unbalanced voltage protection(Unbalanced V)

9

Gas tripping protection

10

PT Break Judgment

measure function

Index

Electrical parameters

Accuracy

1

secondary & primary protection current value(Ia, Ic)

1%

2

secondary & primary measure voltage value(Uab,Ubc£©

1%

3

frequency£¨F£©

0.02Hz

4

power£¨P¡¢Q£©secondary & primary value£»power factor£¨COS¡é£©

3%

control function

Index

Item

Remarks

1

breaker control

through the menu operation

2

Relay for trip

The device provides 5 output relays used to control the output and signaling functions.


Ordering instructions

Provide the following upon ordering:

1. Name, model and quantity of the device. Please specify any special requirement differs from our standard product.

2. Voltage class. The operating power supply for any device is intended for both AC and DC purposes, with 110V and 220V inputs; the 220V version will be provided unless otherwise specified.

3. Communication port: The device standard communication configure is a single 485. If needs dual RS485 network which shall be specified.

4. Ratings of key parameters

For a protector, provide the nominal rated current (1Aor5A)

For a device with the zero sequence current protection function in a low-current ground system, provide the rated zero sequence current (0.2Aor0.02A)

5. Term and place of delivery, means of transport

6. Other terms shall be negotiated.

Copyright  2006-2016 Zhuhai Hengrui Power Technology Co.,Ltd All Rights Reserved. ‚䰸̖:»›ICP‚ä2023083886Ì–
Tel£º0756-2251627 Fax£º0756-8595799 Email£ºhero@zh-hero.com Code£º519000